3.3 Definitions and Wring of PLC Board Interface

                                                                                            Figure 3.9 PLC Board

3.3.1 Basic Specifications

Table 3.8 Basic parameters of PLC Board

Storage and transportation conditions

Temperature

-40~70℃

Relative Humidity

<=95%, No condensation

Atmospheric pressure

70~106kpa

Sinusoidal Vibration

<=10 m/s2 , Three-axis direction Acceleration

Random Vibration

<=1 M2/s3,Acceleration spectral density

Allowed drop height

<=1 M

Others

No corrosive gases, No dust

Working conditions

Temperature

5~45℃

Relative humidity

10%~95%,No condensation

Atmospheric pressure

80~106kpa

Sinusoidal vibration

<=10 m/s2,Three-axis direction Acceleration

Vibration frequency

<=900Hz

Random Vibration

<=1 M2/s3,Acceleration spectral density

Others

No corrosive gases, No dust

3.3.2 Interface definitions

Figure 3.9 Interface definitions of PLC Board

Number

Name

Technical description

1

Power-supply interface

DC 24V(It is better by using two + terminals power-supply when the output load is large)

2

ECAT Bus input interface

Recommend: port IN access output port of the front ECAT controller, port OUT access input port of the rear ECAT controller.

3

ECAT Bus output interface

4

Bus state indicators

See the following table about Bus state indicators definition

5

Board state indicators

See the following table about Board state indicators definition

6

Digital output interface

PLC32:with 32 input ports and 32 output ports

PLC48:with 48 input ports and 48 input ports

8

Digital output interface

7

Digital output state indicator

When interface is in state of logic level '1', the corresponding LED is ON. Otherwise the corresponding LED is OFF.

9

Digital input state indicator

3.3.3 Bus State indicators

Figure 3.10 Bus State indicators

LED Name

Function

State

Meaning

ACT1

Connection state of OUT port

OFF

OUT port is NOT effectively connected with other devices

Constantly ON

OUT port is effectively connecting with other devices

Blinking

OUT port is communicating with other devices

ACT0

Connection state of IN port

The same as ACT1

The same as ACT1

RUN

Bus State indicators

OFF

Board is not established connection with Bus, or it is in the INIT state.

Blinking

Board-Bus is in the PRE-OP state, it is an intermediate state when the power is on.

Constantly ON

Board-Bus is in the OP state, which is the state of normal operation

3.3.4 State indicators of PLC Board

Table 3.11 State indicators of PLC Board

LED Name

Function

State

Meaning

PWR

Power indicator

Constantly ON

Board power supply is in normal.

PLD RUN

Port IO working state

Blinking

Port IO Chip is working in normal.

CFG ERR

Bus configuration state

OFF

Bus control chip is configured in normal.

ON

Bus control chip is configured in ERROR

CUP RUN

Board CPU working state

Blinking

Board control chip is working in normal.

COMM

Communication state indicator

OFF

No process data is exchanging between the Board and the main station.

Constantly ON with low

luminance

Process data is exchanging between the Board and the main station.

RES

Reserved

 

 

3.3.5 Wiring examples and Principles of Interface

Overview

                                                                                    Figure 3.10 Wiring of the PLC Board

Interface circuit

ESCPLC-ASIC-V1.3 has the input with 24V electrical level, and the input signal and the power supply of the entire Board interface are grounded together. Its basic parameters are as follows:

ESCPLC32-ASIC-V1.3

32 digits inputs, 32 digits outputs

ESCPLC48-ASIC-V1.3

32 digits inputs, 32 digits outputs

The input signal is a kind of level input, and the signal should be grounded together with the power signal of the Board interface. The typical input current is <2mA. It is suitable for driving small power relays and LED. See more in the following figure:

Electrical level or Voltage

State

Vin>19V

Logic '1'

6V<Vin<19V

The same as former logic state

Vin<6V

Logic '0'

The output signal is driven by transistor, and its driving current is from the power supply of Board interface. The referential electrical level is from the negative pole of the power supply of the Board. The driving voltage is 24V, and maximum driving current is 200mA, so it can be used only to drive small power relays and signal lights. See more in the following figure:

The output logic state

The output voltage

Logic '1 '

VCC(24V power supply voltage of the Board), Output Current is <200mA

Logic '0 '

<1V

Wiring example of the PLC Board

                                                                    Figure 3.11 Wiring example of the PLC Board

0 (0)
Article Rating (No Votes)
Rate this article
Attachments
There are no attachments for this article.
Comments
There are no comments for this article. Be the first to post a comment.
Full Name
Email Address
Security Code Security Code
Related Articles RSS Feed
3.1 Descriptions and Wiring of CNC Interface
Viewed 8811 times since Wed, Aug 24, 2016
2.1 Installation of CNC BOX
Viewed 3529 times since Wed, Aug 24, 2016
1.1 All-analog control
Viewed 2203 times since Wed, Aug 24, 2016
2.4 Installation of Driver, Motor and Accessories
Viewed 4067 times since Wed, Aug 24, 2016
3.2 Definitions and Wiring of DAC Board Interface
Viewed 38306 times since Wed, Aug 24, 2016
1.3 All-digital control
Viewed 2371 times since Wed, Aug 24, 2016
1.2 Analog spindle & Digital servo-control
Viewed 3057 times since Wed, Aug 24, 2016
2.3 Installation of PLC Board
Viewed 1918 times since Wed, Aug 24, 2016
2.2 Installation of DAC Board
Viewed 2358 times since Wed, Aug 24, 2016
1. i5 System Brief description
Viewed 2373 times since Wed, Aug 24, 2016